Water Chiller Plant - 3tr To 300tr Capacity, Fully Automatic Air/water Cooled Models With Safety Measures
Price:
Get Latest Price
In Stock
Product Specifications
Model | Cc-Ch-3 To Cc-Ch-120 |
Capacity | 9000-360000 Kcal/Hr |
Flow Rate | 30-1200 Liters/Min |
Min Temp | +6 To -5 C |
Power | 4-145 Kw |
Voltage | 415V, 3 Phase, 50Hz |
Material | Steel |
Features | Fully Automatic, Water/Air Cooled, Wide Capacity Range, Robust Construction, Safety Measures, Efficient Cooling, Reliable Operation |
Product Overview
Key Features
Bringing our the most advanced solutions for chilling applications, we are manufacturing and supplying a highly functional Water Chiller Plant. Available in both air and water cooled models, these plants are fully automatic in their operations. In accordance with the global standards, the plant is installed in core industries for varied chilling applications. We have all the facilities and tools to inspect the Water Chiller Plant on standard quality parameters.
Features
- Available in 3TR to 300Tr range of capacity
- Safety measures installed
- Robust construction
MAIN FEATURES
- Fully automatic Water/Air Cooled
- Open/Hermetic Compressor (Optional)
- Wide range of Capacity from 3 TR to 300 TR
- Main parts are designed and manufactured by Cool Command
- Compressor, Motor, Extension Valve, HP/LP switches, Temperature controller, Electrical Control, Dryer, etc. of interlocks for all major faults conditions.
Model No. | Capacity (k cal/hr) | Flow Rate (liter/mins) | Minimum Temp.(C) | Power (kw) |
CC-CH-3 | 9000 | 30 | +6 | 4 |
CC-CH-4.5 | 13500 | 45 | +6 | 6 |
CC-CH-6 | 18000 | 60 | +4 | 8 |
CC-CH-8 | 24300 | 80 | +4 | 10 |
CC-CH-10 | 30000 | 100 | -3 | 13 |
CC-CH-12 | 36600 | 122 | -3 | 15 |
CC-CH-15 | 45000 | 150 | -3 | 19 |
CC-CH-16 | 48600 | 160 | -3 | 20 |
CC-CH-18 | 54300 | 180 | -3 | 23 |
CC-CH-20 | 60000 | 200 | -3 | 26 |
CC-CH-24 | 73500 | 245 | -3 | 32 |
CC-CH-30 | 90000 | 300 | -3 | 39 |
CC-CH-40 | 120000 | 400 | -5 | 52 |
CC-CH-60 | 180000 | 600 | -5 | 75 |
CC-CH-90 | 270000 | 900 | -5 | 110 |
CC-CH-120 | 360000 | 1200 | -5 | 145 |
- Capacities based on 7C evaporating temperature.
- Flow rate Calculated considering a of 5C.
- Power required 415 V 3 phase 50 Hz.
- 10% cooling capacity increase in water cooled system.
- Due to continuous R&D, the above information is subject to change without notice.
CALCULATIONS FOR REQUIRED COOLING ENERGY
First Step for proper selection of Chiller is done by knowing quantity of heat to be dissipated. To find out heat dissipated, use of following formula is made. Heat to be dissipated (KCal/hr) Flow of the liquid (Kg/hr) T(Temp. difference in inlet & outlet of fluid ) Specific heat of the liquid | Heat = Kh/hr X Spec. Heat X ( t out - t in) For water and glycol the spec. heat is 1 and 1 Kg is equivalent to 1 liter. Calculation Example for water: Water flow in the circuit 2000 I/hr. Heat = 2000 x 1 x (25-20) = 10,000 Cal/hr. 1 TR = 3000 KCal/hr 1 TR = kw x 0.286 |
Company Details
Focusing on a customer-centric approach, COOL COMMAND ENGINEERS has a pan-India presence and caters to a huge consumer base throughout the country. Get Cooling Tower & Chilling Plants from COOL COMMAND ENGINEERS at Trade India quality-assured services.
Business Type
Manufacturer, Service Provider, Supplier
Employee Count
15
Establishment
1995
Working Days
Monday To Sunday
Related Products
Explore Related Categories
More Product From This seller
Seller Details
Noida, Uttar Pradesh
Accepts only Domestic inquiries
Ceo
Mr. Chandra Kant Singh
Address
T-7, Shree Jee Complex, Sharma Market, Harola, Sector 5, Noida, Uttar Pradesh, 201301, India
water chiller in Noida
Report incorrect details