Automatic Voltage Control Units
Price:
Get Latest Price
In Stock
Product Specifications
| Input Voltage | 200 V ac |
| Frequency | 400 Hz |
| Output Voltage | 80 V dc |
| Current | 6 Amps dc |
| Field Resistance | 10 ohms |
| Regulation | +/- 1% |
| Size | 140x145x45 |
| Features | Voltage regulation, Harmonic reduction, Stable operation, Quick response, Durable design, Easy installation, High insulation, RFI suppression |
Product Overview
Key Features
Leveraging on our skilled manpower and state-of-the-art infrastructure, we are occupied in manufacturing, supplying and exporting Automatic Voltage Control Units. We manufacture these control units by efficient use of quality tested components and sophisticated tools; while the hardware circuit is rigorously tested on various quality parameters. Widely used in CMOS circuit designing, electric, switchgear and semiconductor industries; our products are helpful in uniform distribution of L-C type network. Further, these are helpful in eliminating voltage over-drop and harmonic distortion. Offered Automatic Voltage Control Units are highly acknowledged for the below enlisted attributes:
- Durable construction
- Protected against rust and wearing
- High insulation properties
- Reduced level of heat transfer
- Quick and error free measurement system
Further details:
Model- AX-02
Technical Specifications:
| Input Power Voltage | : 200 V ac rms +/- 10% |
| Frequency | : 400 Hz |
| Output Power Voltage | : 80 V dc at 200 V a.c. input |
| Current | : 6 Amps dc, 8 Amps for 10 secs for motor starting. |
| Field Resistance | : 10 ohms, minimum |
| Build up | : Less than 5V a.c. rms at VCU power input terminals. |
| Regulation | : +/- 1% of set voltage |
| Voltage Adjustment | : +/- 10% over 200V |
| Stability Adjustment | : Adjustable to get stable operation and desired response. |
| Voltage Sensing | : 200 V a.c. two line sensing. VCU senses average of the generator wave form. |
| Response time | : Less than75 milli seconds. |
| Under frequency Protection (FRO) | : Adjustable from 350Hz to 450Hz. |
| Circuit Protection | : Protection against voltage transients by L-C networks and high energy suppressors. |
| RFI Suppression | : VCU includes RFI filters to filter out the RFI generated due to power device turn on. |
| Temperature drift | : Typically 0.025% per degree celcius over operating temperature range. |
| Fuse | : 4 amps fuse provided inside the VCU box. |
| Operating temperature | : -20 degree celcius to + 60 degree celcius ambient. |
| Power dessipation | : 10 watts (max) |
| Size (LBH) | : AX02 : 140x145x45 |
| Weight | AX02 : 700 gms |
Company Details
Focusing on a customer-centric approach, ALTEX ELECTRIC CO. has a pan-India presence and caters to a huge consumer base throughout the country. Get Electrical Goods, Equipment & Supplies from ALTEX ELECTRIC CO. at Trade India quality-assured services.
Business Type
Exporter, Manufacturer, Service Provider, Supplier
Employee Count
20
Establishment
1997
Working Days
Monday To Sunday
Certification
ISO 9001:2000
Related Products
Explore Related Categories
More Product From This seller
Seller Details
Bengaluru, Karnataka
Ceo
Mr. Mohit Arun Kumar
Address
No.1297, 14/2 First floor, 24th Main Road, KHB colony, Govindraj Nagar, Bengaluru, Karnataka, 560079, India
automatic voltage controllers in Bengaluru
Report incorrect details