Mpt Series Line Interactive Ups
Price:
Get Latest Price
In Stock
Product Specifications
| Capacity | 0.5-2.0 kVA |
| Input Voltage | 160-280V |
| Input Frequency | 50Hz |
| Waveform | Stepped sine |
| Output Voltage | 230V |
| Efficiency | 70% |
| THD | 40% |
| Usage | Computer and general purpose applications |
| Switching Time | 10ms |
| Protection | Overload, short circuit |
| Charger | Dual rate CV/CC |
| Features | Clean power, Fast sensing, Long battery life, Overload protection, AVR included |
Product Overview
Key Features
MPT Series Line Interactive UPS
The MPT Series UPS range is specially designed to provide clean power to sensitive electronic systems. It has built- in EMI filter and a special fast-sensing circuit for switching over to battery operation in case of unhealthy mains input.
A wide range of mains input voltage variation is corrected without requiring changeover to batteries to enhance battery life. The UPS output is a stepped approximation to Sine wave. PWM thereby maintaining UPS output voltage within safe limits. A piezzo-buzzer alarm and various visual indications are provided for operator convenient Output overload and short-circuit protection is provided by electronic current- limiting and fuse. Change over from battery to mains operations is internally delayed to provide mains stabilization. A dual rate CV/CC charger charges SMF as well as higher AH automotive batteries.
Optional Features
- Microprocessor based design
- Built-in AVR
- Green inverter
- Computer interface port for UPS monitoring software
- Multi-function LED display
- Cold start provided
- Compact size
Technical Specifications
Capacity
0.5 KVA to 2.0 KVA
Application
Line Interactive UPS with AVR for computers and general purposes
Input Voltage Range
160 to 280 V, Single Phase AC (as per requirement)
Input Frequency
50+ 3 Hz
Wave Form
Stepped approximation to Sine wave
Output Voltage
AVR output voltage in AC mode: 230 V 9%, 503 Hz.
UPS output voltage in battery mode: 230 V 10%. 500.5 Hz at load power factor of not less than 0.6 lag
Switching Device
MOSFET/ IGBT
Switching Frequency
Above 50 Hz
Switching Overtime (From AC mains to UPS mode on power failure)
10 milliseconds (Maximum)
Efficiency (at rated output voltage and frequency)
Inverter efficiency : Miniumum 70%
Regulation
Total variation of voltage form no load to full load will not exceed 10%
Total Harmonics distortion
40% Maximum (in DC mode)
Overload
Withstands 10% overload for at least 10 mins. in mains mode
Protections
If input voltage goes outside the range 160 to 280 V, the system will switch over to battery mode Over voltage. Short circuit and Overload at UPS output terminals Protection against over discharge (The load will be cut~off as soon as voltage of battery terminals falls below 10.5 V for 12 V and 21 V for 24 V battery systems)
Indicators and Meters
- Mains mode
- UPS mode
- Battery low,over load
General
- Ambient temperature: 0 to 55C
- Relative humidity: Upto 95% non-condensing.
- as per customer requirement
Company Details
Focusing on a customer-centric approach, MICRO POWER TECHNOLOGY PVT. LTD. has a pan-India presence and caters to a huge consumer base throughout the country. Buy UPS & Power Supply in bulk from MICRO POWER TECHNOLOGY PVT. LTD. at Trade India quality-assured products.
Business Type
Manufacturer, Supplier
Employee Count
30
Establishment
2009
GST NO
09AAICM6734C1ZF
Related Products
Explore Related Categories
More Product From This seller
Seller Details
GST - 09AAICM6734C1ZF
Noida, Uttar Pradesh
Proprietor
Mr. Jitendra Kumar
Address
C-118 G.F., Sec-65, Noida, Uttar Pradesh, 201301, India
microtek ups in Noida
Report incorrect details