Clean Room Process Monitor - Stainless Steel Modular Faceplate, Measures Rh, Temperature & Differential Pressure, Modbus Rs-485 Communication, Audible & Visual Alarms, User Programmable Settings
Price:
Get Latest Price
In Stock
Product Specifications
| Inputs | 3 |
| Display Type | LED |
| Communication | Modbus RTU |
| Power Supply | 20-30VDC |
| Enclosure Material | Stainless Steel |
| Mounting | Modular wall |
| Usage | Cleanroom environmental monitoring in pharmaceutical and HVAC applications |
| Features | Humidity monitoring, Temperature sensing, Pressure display, Modular design, Cleanroom ready, Modbus enabled, Audible alarms |
Product Overview
Key Features
Description
The STYRAX Clean Room Process Monitor has been specially developed keeping process measurement requirements of CLEAN ROOMS in Pharmaceutical industries. The Process Monitor can measure Relative Humidity, Temperature and Differential Pressure through inbuilt sensors. It has on demand dew point display. The Monitor has status LEDs for process violation indication. Humidity, Temperature and pressure will display individually and data transfers to any master device on modbus serial communication. It also has communication diagnosis LED. The monitor has inbuilt buzzer for audible process violation. It has keypad to programming the instrument by user. It has Stainless steel Modular Face plate, which is designed as a mounting accessory for monitor suited for Modular wall Clean Room applications where you need flush mounting mechanism. This instrument enables you to measure humidity, temperature and differential pressure in the following fields:
HVAC (Heating, ventilation, Air conditioning, cooling)
Pharmacy industry.
Blood stations, pharmacies.
Horticultural and cultivation of plants.
Features:
Advanced Microcontroller based inbuilt RH, Temperature & DP measurement.
Software programmable channel ranges and unit.
Programmable resolution.
4 Digit, 0.39 bright LED display for displaying DP, RH & Temperature.
Process parameter status indication with 3 LEDs.
User selectable set limits for process value violation.
Inbuilt buzzer to audible process value violation.
Password protection for calibration and programming mode.
Software Calibration for 3 channels.
MODBUS RTU multi drop RS-485 serial communication for PLC, SCADA, etc.
Programmable baud rate.
Diagnosis of Communication with master.
Remote programmable from master device.
User programmable offset correction.
Brick and modular wall mounting.
Stainless steel enclosure.
Specifications:
Input
No. of inputs:
Input RH :
Input T :Integral RH+T sensor
Input DP : Integral RH+T sensor
INDICATION
%RH: Window 2, 4 digit 7 segment 0.39 red LED display
Temperature:Window 2, 4 digit 7 segment 0.39 red LED display
Differential Pressure:Window 2, 4 digit 7 segment 0.39 red LED display
Status indication: LEDs for visual alarms, buzzer for audible alarm, LED for RS-485 communication
MEASURING RANGE
%RH:
Temperature:
Differential pressure: -105.4 105.4 mmWC,
-10.3410.34mbar,
-7.75 7.75 mmHg,
-10.54 10.54 cmH2o,
-4.15 4.15 inch H2o,
-21.6 21.6 Psf (USA),
-10.34 10.34 hPa,
-0.15 0.15 psi,
-1034 1034 Pa,
-1.034 - 1.034 kPa.
| Accuracy : |
| RH : +/- 2%RH of 10-90% |
| 4%RH for remaining |
| Temp : +/- 1deg for 0-40deg |
| +/- 2deg for remaining |
| DP : +/- 1.5% of FSR |
| Response time : 8sec for RH |
| 12sec for Temp |
| 1sec for DP |
| Communication type : RS - 485 isolated |
| Baud rate : 9600/19200/38400 |
| Protocol : MODBUS RTU |
| Power supply : 20-30VDC |
| Enclosure : SS316 faceplate with MS powder coated box |
| Mounting : Brick and Modular wall |
Company Details
Business Type
Manufacturer, Service Provider, Supplier
Employee Count
100
Establishment
2010
Working Days
Monday To Sunday
GST NO
36AANCS6577L1ZF
Related Products
Explore Related Categories
More Product From This seller
Seller Details
GST - 36AANCS6577L1ZF
Hyderabad, Telangana
Managing -director
Mr Ram Bandi
Members since
1 Years
Address
Ho. No 2-77; Sy No 229; Gajularamaram, Hyderabad, Telangana, 500055, India
cleanroom accessories in Hyderabad
Report incorrect details